Heinrichs Electromagnetic Flowmeters 2020-09-01T16:53:26+01:00

Heinrichs Electromagnetic Flowmeters

heinrichs electromagnetic flowmeters

Magnetic Inductive Flow Meter

Model: EPS

Applications

Volume flow measurement of electrically conductive liquids, slurries and pastes without loss of pressure

Special features
  • High accuracy
  • No maintenance required
  • No pressure drop
  • Wide spectrum of electrode materials
  • Many liners available
  • Inexpensive grounding electrode available instead of grounding rings, also available special materials like e. g. tantalum
  • Large selection of process connections
Technical data

Sensor EPS

  • Body: Coated steel
  • Process connection: Steel or stainless steel 1.4301 flanges (EN1092, ASME B16.5 and JIS) Food connection DIN11851, TriClamp® , (others on request)
  • Lining: Hard rubber, Soft rubber, PTFE, EPDM and Ceramic
  • Measuring and grounding electrodes: Stainless steel 1.4571, Hastelloy C276, Tantalum, Platinum (Grounding ring and other materials on request)
  • Nominal diameters: DN15 up to DN 1200 (others on request) 2 / 3 / 6 / 10mm inner diameter with process connection G1/2” (m) or ½” NPT(m)
  • Nominal pressure: PN40/ASME Class 300 for DN15 to DN300
    PN16, ASME Class 150 for DN50 to DN600
    PN10, ASME Class 150 for DN200 to DN1200
  • Process temperature: 
  • -10°C up to +70°C EPDM
  • 0°C up to +95°C Hard rubber (Ebonite)
  • 0°C up to +70°C Soft Rubber
  • -20°C up to +150°C PTFE and Ceramic
  • Ambient temperature: -20 °C to +60 °C, depending on process temperature
  • Conductivity: >5µS/cm ,>20 µS/cm for demineralized water
  • Range limits: 0,5 m/s – 10 m/s
  • Accuracy: ± 0.3 % of measured value ± 0.01 % * (Q at 10 m/s) (under reference conditions)
  • Repeatability: ± 0.15 % of measured value ± 0.005 % * (Q at 10 m/s) (under reference conditions)
  • Ingress protection: Standard IP 67 (EN60529), IP68 on request

Transmitter UMF2

  • Installation: integral or remote
  • Housing: Aluminum die cast, coated
  • Power supply: 115 / 230 VAC 50/60Hz 10VA, 24 VDC 10W

Outputs:

  • Analog: 1 x 0/4-20 mA active, galvanically isolated
  • Pulse: passive, galvanically isolated, 24V, 60mA
  • Status: passive, galvanically isolated, 24V, 60mA
  • Ambient temperature: -20 °C to +60 °C, depending on process temperature (integral installation)
  • Ingress protection: IP67 (EN60529), IP68 on request
  • Diagnostic Functions: Empty pipe detection, exciter current monitoring
  • Electromagnetic compatibility: EMC Directive 2014/30/EU (EMC)
  • Low Voltage directive: 2014/35/EU (LVD)
Communication

4-20mA, HART® Protocol

heinrich Magnetic Inductive Flow Meter ATEX

Magnetic Inductive Flow Meter ATEX

Model: EPX

Magnetic-Inductive flowmeter
for hazardous areas
Applications

Volume flow measurement of electrically conductive liquids in hazardous areas without pressure loss.

Special features
  • ATEX approval
  • High accuracy
  • No maintenance required
  • No pressure drop
  • Wide spectrum of electrode materials
  • Many liners available
  • Inexpensive grounding electrode available instead of grounding rings, also available special materials like e. g. tantalum
  • Large selection of process connections
Technical data

Sensor EPX

  • Body: carbon steel painted Ex IIG or st.st. Ex IID
  • Process connections: carbon steel or st.st. flanges (1.4301 / SS316) EN1092 und ASME
  • Lining: hard rubber, soft rubber, E-CTFE, PTFE,
  • Measuring and grounding electrodes: st.st. 1.4571, hastelloy, tantalum, platinum (Grounding ringa and other materials on request)
  • Nominal diameters: DN15 (1/ 2 inch) up to DN 300 (12 inch)
Nominal pressure
  • PN40, ASME Cl150/300 DN15 (1/2 inch) up to DN50 (2 inch)
    PN16, ASME Cl150 DN65 (2 ½ inch) uzp to DN200 (8 inch)
    PN10, ASME Cl150 DN250 (10 inch) bis 300 (12 inch) (higher on request)
  • Process temperature:
    Hard rubber -35….+64°C(T6)
    Soft rubber +5…..+64°C (T6)
    PTFE -35…+64°C (T6) ..+79°C(T5) ..+114°C(T4) ..+139°C(T3)
  • Ambient temperature: -35°C …. +60°C
  • Conductivity: >5 µS/cm
    >20 µS/cm for demineralized water
  • Range limits: 0,1 m/s – 10 m/s
  • Accuracy: ±0,3% of actual ±0,01% (Q at 10m/s) (under reference conditions)
  • Repeatability: ±0,15% of actual ±0,005% (Q at 10m/s) (under reference conditions)
  • Ingress protection: IP67 (EN60529), IP68 on request
Transmitter

UMF3

  • Installation: integral or remote
  • Housing: aluminum die cast, coated
  • Power supply : 90…253V AC 50/60Hz, 24V DC ±20%
Outputs
  • Analogue: 1x 0/4-20mA HART, passive, galvanically seperated
  • Pulse output: passive, galvanically seperate, Um=30VDC
  • Status output: passive, galvanically seperate, Um=30V,
  • Ambient temperature: -20°C …. +60°C
  • Ingress protection: IP67
  • Diagnosis function: empty pipe detection, coil current monitoring
Hazardous Area Protection

Ex II(1G) 2G Ex d e [ia Ga] IIB T6/T4/T3 Gb
Ex II(1G) 2D Ex tb IIIC [ia Ga] T80 °C / T125 °C / T 150 °C Db

Communication

HART® protocol

mgi_02

Magnetic Inductive Flow Meter

Model: EP

Applications

Volume flow measurement of electrically conductive liquids, slurries and pastes without loss of pressure.

Special features

  • High accuracy
  • No maintenance required
  • No pressure drop
  • Wide spectrum of electrode materials
  • Many liners available
  • Inexpensive grounding electrode available instead of grounding rings, also available special materials like e. g. tantalum
  • Large selection of process connections
Technical data

Sensor EP
Body: Coated steel
Process connection: Steel or stainless steel 1.4301 flanges (EN1092 und ASME B16.5),
Flangeless connection (wafer), food connection DIN11851,
TriClamp® , (others on request)
Lining:Hard rubber, soft rubber, PTFE, Rilsan (in preparation),
PFA (in preparation),Wagunit
Measuring and grounding electrodes: Stainless steel 1.4571, Hastelloy C4, Tantalum on request, Platinum;
Grounding ring and other materials on request

  • Nominal diameters: DN15 bis DN 300 (others on request)

Nominal pressure:

  • PN 40, ASME Cl150 / 300 DN15 to DN50
  • PN 16, ASME Cl150 DN50 to DN200
  • PN 10, ASME Cl150 DN250 to DN300(higher pressure rates on request)

Process temperature:
0 °C to +80 °C (hard rubber, soft rubber, PFA)
-20 °C to +150 °C (PTFE)
0 °C to +80 °C(Rilsan, Wagunit)
Ambient temperature: -20 °C to +60 °C, depending on process temperature
Conductivity: >5µS/cm ,>20 µS/cm for demineralized water
Range limits: 0,5 m/s – 10 m/s
Accuracy: ± 0.3 % of measured value ± 0.01 % *
(Q at 10 m/s) (under reference conditions)
Repeatability: ± 0.15 % of measured value ± 0.005 % *
(Q at 10 m/s) (under reference conditions)
Ingress protection: IP 67 (EN60529), IP68 on request
Transmitter UMF2
Installation: integral or remote
Housing: Aluminum die cast, coated
Power supply: 115 / 230 VAC 50/60Hz 10VA, 24 VDC 10W
Outputs:
Analog: 1 x 0/4-20 mA active, galvanically isolated
Pulse: passive, galvanically isolated, 24V, 60mA
Status: passive, galvanically isolated, 24V, 60mA
Ambient temperature:-20 °C to +60 °C, depending on process temperature (integral installation)
Ingress protection: IP67 (EN60529) Diagnostic Functions: Empty pipe detection, exciter current monitoring
Electromagnetic compatibility: EMC Directive 89/336/EWG

Communication

4-20mA, HART® Protocol

HH
HEINRICH EMFM2

Magnetic Inductive Flow Meter

Model: PIT

Electromagnetic Insertion Sensor
Applications

Volume flow measurement and monitoring of electrically conductive liquids, slurries and pastes.
Suitable for fluids which tend to fat films or crusts.

Special features
  • Low cost alternative to traditional in-line devices
  • Suitable for pipe diameters up to DN 2000
  • Under operating conditions mountable or dismountable,
  • Used in hazardous areas

Technical data

Sensor
Materials:
Body: Stainless steel / PTFE, PFA (others on request).
Electrodes: Hastelloy, Tantalum, Platinum, (others on request)

End connections: flanges acc. EN 1092, ASME B16.5, DIN2512, (others on request)

Nominal pressure: PN 16, ASME Cl150 / 300 (stainless steel / PTFE) PN 40, ASME Cl150 / 300 (PFA) (others on request)

Process temperature: -40°C up to +100°C (stainless steel / PTFE) -40°C up to +150°C (PFA)

Ambient temperature: -40°C up to +60°C

Ingress protection: IP 65 / IP 68 (EN60529)

Range of application
For sizes: DN125 up to DN2000 (stainless steel / PTFE)
DN125 up to DN600 (PFA)

Range limits standard: 1 m/s – 10 m/s , Special: 0,5 m/s – 5 m/s

Transmitter
UMF – UMF2
Installation: integral or remote

Power supply: 115 / 250 VAC (UMF, UMF2)
24 VDC (UMF, UMF2)
24 VAC (UMF)

Outputs: galvanically isolated
Analog: 2 x 0/4-20 mA (UMF)
1 x 0/4-20 mA (UMF2)

Binary 1: active, potential free 24 V=, max. 200 mA (UMF)
passive, optocoupler, (UMF, UMF2)
Ui=30 V, Ii=200mA, Pi=3 W

Binary 2 (status): passive, optocoupler, (UMF)
Ui=30 V, Ii=200mA, Pi=3 W

Binary 3 (optional): passive, optocoupler, (UMF)
Ui=30 V, Ii=200mA, Pi=3 W

Ambient temperature: -20°C up to +60°C
Ingress protection: IP 68 (EN60529)
Accuracy: ± 1,5% of reading ± 0,5% from upper range value

Approvals and certificates

Explosion protection:
Sensor: BVS 03 ATEX E 150 X
II 2G EEx e[ia] IIC T3-T6
NEPSI Approval Cert. No. GYJ06474X

Transmitter: DMT 99 ATEX E 107 (UMF)
Increased safety EEx e (connection): II (1)2G EEx de[ia] IIB/IIC T3-T6
Explosion proof:EEx d(connection II (1)2G EEx d[ia] IIB/IIC T3-T6
Signal out- inputs: intrinsically safe / not intrinsically safe
NEPSI Approval Cert No. GYJ06475

CE-Mark: Explosion Protection Directive 94/9/EC
EMC-Directive 89/336/EEC

Communication

4-20 mA, HART® protocol (UMF, UMF2)

HEINRICH MIFM PITE

Magnetic Inductive Insertion Flow Sensor

Model: PITe

Applications

Volume Flow measurement and monitoring of electrically conductive liquids. ECONOMIC sensor version for larger pipe sizes up to DN 400 / 16 inch.

Special features
  • ECONOMIC version with weld-on adapter
  • Low cost alternative for classic in-line meters
  • Suitable for pipe diameter up to DN 400 / 16 inch
  • Sensor installation and removal with threaded quick release

Technical data

Materials

  • Sensor body: st.st. / sensor tip PTFE
  • Electrodes: st.st. / hastelloy
  • Process connection: weld-on adapter with cap nut sensor fixing
  • Nominal pressure: PN16
  • Pipe sizes: DN 80/3“ ….. DN 400/16“
  • Process temperature: -20°C …. +100°C
  • Ambient temperature: -20°C ….. +60°C
  • Ingress protection: IP65 / IP68
  • Range limitations: 1 m/s…..10 m/s
Transmitter

UMF2 – remote mounting

Power supply: 115 / 250VAC / 24 VDC

Output signal galvanically separated )

  • 1x 0/4-20mA, HART
  • 1x status output, passive
  • 1x pulse output, passive
  • Ambient temperature: -40°C …. +60°C
  • Ingress protection : IP 65 / IP68 (EN60529)
  • Accuracy:
    at (Q≥30% of URV): ± 1,5% of actual
    at (Q≤30% of URV): ± 1,5% of actual ± 2,5% URV
    (under reference conditions)
  • Repeatability: ± 0,75%
    (under reference conditions)
Approvals and certificates

CE- marking,
EMC guide line 2014/30/EU

Communication

HART® protocol

HEINRICH MIFM MIK

Magnetic Inductive Flow Meter

Model: MIK

Application

Volume flow measurement of electrically conductive liquids, acids and caustic liquids. without pressure loss

  • Drinking, cooling and waste water
  • Ground water, tap water
  • Machine building
  • Chemical industry / laboratory use
  • Automotive
Special Features
  • Compact OEM version
  • Wear free
  • without pressure loss
  • Sensor body made from PPS or PVDF
  • Large selection on electrode meterials
  • Large selection of process connections

Technical data

  • Sensor body: PPS c/w sxt.st. electrodes ; PVDF c/w hastelloy- oder tantalum-electrodes, sealing NBR, FPM, FFKM
  • Process connections: G ½  AG …G 2 ¾ AG
  • Connection sets: PVC – glue connection or hose connection, weld-on set st.st.
  • Lining free version as sensor body base material is PPS or PVDF
  • Measuring electrodes: st.st. 1.4401, Hastelloy C4, Tantalum,
  • Max. pressure: 10 bar
  • Process temperature: -10°C up to +80°C ( max. 60°C for PVC connections )
  • Ambient temperature: -10°C up to +60°C
  • Conductivity: >30 µS/cm
  • Max. media viscosity: 20 cSt ≤ G1“ ; 70 cSt ≥G 1 ½“
  • Flow Ranges: 0,01-0,5 ….35-700 l/min
  • Meas. Accuracy: ±2% FS
  • Repeatability: ±1% FS
  • Response time: ~ 1s
  • Protection: IP65
Elektronic versions

› FREQUENCY OUTPUT

  • F300    M12 Plug, 500 Hz
  • F390    M12 Plug, 50…1000 Hz

› SWITCHIN OUTPUT

  • S300    M12 plug, relay output
  • S30D    M12 plug. active 24 VDC

› ANALOG OUTPUT

  • L303    M12 plug, 0-20 mA
  • L343    M12 plug, 4-20 mA
  • L443    DIN plug, 4-20 mA

› COMPACT ELECTRONICS

  • C30R    M12 plug, 2x open coll. PNP
  • C30M    M12 plug, 2x open coll. NPN
  • C34P    M12 plug, 0(4)-20 mA, 1x open coll. PNP
  • C34N    M12 plug, 0(4)-20 mA, 1x open coll. NPN

› COUNTER ELECTRONICS

  • E14R    1m cable, LCD, 0(4)-20 mA, 2x Relay,
  • E34R    M12 plug, LCD, 0(4)-20 mA, 2x Relay,
  • E94R    M12 plug + 1m cable, LCD, 0(4)-20 mA, 2x relay,

› DOSING ELECTRONCIS

  • G14R    1m cable, LCD, 0(4)-20 mA, 2x relay
  • G34R    M12 plug, LCD, 0(4)-20 mA, 2x relay,
  • G94R    M12 plug + 1m cable, LCD, 0(4)-20 mA, 2x relay
HEINRICH MIFM UMF 2

Transmitter for magnetic inductive sensors

Model: UMF 2

Applications

Transmitter for all Heinrichs sensors series EP and PIT

Technical data

Installation: integral or remote

Housing: Die-cast aluminum, painted

Power supply:: 115/230 VAC 50/60Hz, 10VA
24VDC, 10W

Outputs:

  • Analog: 1x 0/4-20mA active, galvanically isolated
  • Pulse: passive, galvanically isolated, 24V, 60mA
  • Status: passive, galvanically isolated, 24V, 60mA


Ambient temperature: -20°C up to +60°C

Ingress protection: IP67

Diagnostic functions: Empty pipe monitoring, Coil current monitoring

EMC-Directive 89/336/EEC

Flow: 0,1m/s upto 10m/s

Accuracy: 0,5% of reading

Conductivity :> 5µS/cm

Communication

4-20 mA, HART® protocol

HEINRICH MIFM UMF3

Transmitter for magnetic inductive sensors

Model: UMF3

Magnetic-Inductive flowmeter
for hazardous areas
Applications

Transmitter for magnetic inductive flow sensors series EP, EPX and PIT
Special features

  • Full text indication menu structure
  • 6 set buttons “Easy Operation System”
  • For the use in hazardous areas
  • Totalizer for flow and reflow
  • Empty pipe detection, exciter current monitoring
  • Remote or compact installation

Technical data

Installation: integral or remote
Power supply: 90…265VAC 50/60Hz, 19..36 VDC
Ambient temperature: -20°C up to +60°C
Ingress protection: IP68 (EN60529)

Outputs:
  • Analog: 1 x 0/4-20 mA HART passive, galvanically isolated
  • Pulse: passive, galvanically isolated, Um=30VDC
  • Status: passive, galvanically isolated, Um=30VDC
  • Diagnostic Functions: Empty pipe, exciter current
Approvals

Explosion protection
Ex II(1G) 2G   Ex d e [ia Ga] IIB T6/T4/T3 Gb
Ex II(1G) 2D   Ex tb IIIC [ia Ga] T80 °C / T125 °C / T 150 °C Db

Communication

4-20 mA, HART® Protocol