Locate abnormal heat patterns on electrical and mechanical assets before that heat becomes a failure.
Infrared Thermography and Load-Based Survey
Infrared thermography is a non-contact, non-destructive technique that measures the surface temperature of equipment and converts it into a visible map of heat flow. A hot spot is a symptom rather than a fault, so the value of the survey lies in measuring how far a reading departs from its reference, comparing it against its three-phase siblings and against its own history, and identifying the cause behind it.
Surveys are only reliable under load. An electrical panel at no load looks almost identical to a healthy one, and a motor that is cool at rest can still be badly unbalanced under duty. We therefore agree the operating condition in advance, load the equipment to a representative duty, allow thermal conditions to stabilise, and record the load against every measurement. That is what makes one survey comparable with the next, and what allows a rising trend to be caught before an alarm fires.
Thermographic survey detects:
- Loose connections, compression lugs and poorly torqued joints generating resistive heating
- Overloaded conductors, cables and switchgear rated below the load they are carrying
- Phase imbalance and single-phase loading on three-phase systems
- Induced heating from harmonics, stray flux or proximity to adjacent current-carrying conductors
- Blocked or fouled cooling paths, obstructed radiators and degraded fan performance
- Insulation and refractory deterioration, and localised loss of thermal protection
- Hot spots at terminations, joints and fuses inside switchboards and motor control centres
Thermographic Survey Applications
Thermographic survey is applied to:
- Switchboards, motor control centres, distribution boards and panel interiors
- Busbars, cable terminations, joints, lugs, compression connectors and fuses
- Power transformers, including bushings, radiators and tap changers
- Cables in trenches, on trays and at route joints
- Motors, generators, pumps and driven equipment
- Heat exchangers, cooling fin paths, radiators and lagging
Every survey records the thermal image, the measured temperature, the temperature difference against reference and the rise over ambient, alongside a severity rating based on the applicable standard and the equipment class. Findings are priority ranked so the most urgent action comes first, the likely cause is identified, and a re-survey after corrective action confirms the fault has been cleared.
Other services
Explore the rest of
what we do.
Electric Motor Analysis
Assess the electrical and mechanical condition of motors so developing faults are found before they stop production.
Airborne and Structure Borne Ultrasound
Detect leaks, arcing and failing bearings using high-frequency sound, at ranges that ordinary thermography cannot reach.
Laser Alignment
Correct shaft misalignment with laser tooling, extending bearing and seal life and reducing energy use.
Partial Discharge Analysis
Evaluate insulation condition in critical high-voltage equipment so deterioration is measured before it fails.
Onsite Dynamic Balancing
Correct unbalance in rotating equipment while it runs, without removing the rotor from the machine.
Vibration Analysis
Identify rotating machinery faults and track how equipment condition is changing, route by route and trend by trend.
Equipment Calibration
Maintain confidence in your measurement and control instruments with calibration against traceable standards.
Equipment Rental
Access specialist diagnostic and test equipment for planned work, without the capital cost or the lead time.